Common EST 4 Trouble Codes
- MAP FAULT: The panel has detected an unexpected change in the physical wiring sequence or resistance between addressable Signature Series devices on the data loop.
- NETWORK FAULT: The main control panel has lost its IPv6 network communication with a remote annunciator or another node on the proprietary life safety network.
- GROUND FAULT: A field wire on an initiating loop or notification appliance circuit has made unauthorized contact with a grounded metal surface or conduit.
- OPEN CIRCUIT: A complete physical break in the wiring has been detected, preventing the loop controller from polling the downstream modules.